 Current Transducer LB 1000-SI/SP2
For the electronic measurement of currents : DC, AC, pulsed..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN
=
1000 A
Electrical data
IPN IP RM Primary nominal r.m.s. current Primary current, measuring range Measuring resistance with 15 V ISN KN VC IC Vd @ 1000 A max @ 1500 A max 1000 0 .. 1500 RM min RM max 0 0 25 5 A A mA V mA kV
Features
* Closed loop (compensated) current
transducer using the Hall effect
* Insulated plastic case recognized
according to UL 94-V0.
Secondary nominal r.m.s. current Conversion ratio Supply voltage ( 5 %) Current consumption R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
200 1 : 5000 15 21 + IS 6
Special features
* Better zero crossing performance * TA = + 10C .. + 50C * Shield between primary and
secondary.
Accuracy - Dynamic performance data
XG
L
Overall accuracy @ IPN , TA = 25C Linearity Offset current @ IP = 0, TA = 25C Thermal drift of IO + 10C .. + 50C Response time 1) @ 90 % of IP max di/dt accurately followed Frequency bandwidth (- 1 dB)
0.3 < 0.1 Typ Max 0.4 0.2
% % mA mA s A/s kHz
Advantages
* * * * * * *
Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference * Current overload capability.
IO IOT tr di/dt f
0.1
<1 > 50 DC .. 100
General data
TA TS RS m Ambient operating temperature Ambient storage temperature Secondary coil resistance @ TA = 70C Mass Standards 2) + 10 .. + 50 - 25 .. + 85 40 700 EN 50178 C C g
Applications
* AC variable speed drives and servo
motor drives
* Static converters for DC motor drives * Battery supplied applications * Uninterruptible Power Supplies
(UPS)
* Switched Mode Power Supplies
(SMPS)
* Power supplies for welding
applications. Notes :
1) 2)
With a di/dt of 100 A/s A list of corresponding tests is available 000901/0
LEM Components
w w w.lem.com
Dimensions LB 1000-SI/SP2 (in mm. 1 mm = 0.0394 inch)
Front view Left view
Secondary terminals
Terminal + : supply voltage + 15 V Terminal M : measure Terminal - : supply voltage - 15 V
Connection
Top view Mechanical characteristics
* * * *
General tolerance Fastening Primary through-hole Connection of secondary 0.5 mm 4 slots 7 mm 40 mm Faston 6.3 x 0.8 mm.
Remarks
* IS is positive when IP flows in the direction of the arrow. * Temperature of the primary conductor should not exceed
100C.
* Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.


▲Up To Search▲   

 
Price & Availability of LB1000-SI

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X